Configurator

CALL-BACK

We call you back!
Phone number:

 

Detection Range


Detection range is the distance necessary between the active surface of the proximity switch and the object to cause a change in the state of the output (Fig. 9).

 

 

 

Correction Factor


Inductive: When using inductive proximity switches with non-ferrous metals it is necessary to apply a correction factor to the detection range specification as follows:

Brass D x 0,5
Aluminium D x 0,45
Copper D x 0,4
Chrom Nickel Alloy D x 0,9
Stainless Steel D x 0,85

Capacitive: With capacitive proximity switches detection range is usually adjustable and dependent on the type of material to be sensed (Fig. 10).

Optical: With optoelectronic proximity switches, the detection range is usually adjustable and is dependent on the reflective index of the material to be sensed, ie:

Styrene plastic, white approx. 1
Polished metal approx. 1,2 - 2
Aluminium, black anodized approx. 1,1 - 1,8
PVC, gray approx. 0,5 - 0,7
Wood, unfinished approx. 0,4 - 0,7
Cardboard approx. 0,1 - 0,2

 

 

 

Zeichenkodierung

flash mountable
  flash mountable with increades detection range
flash mountable and stackable
not flash mountable
A Aluminium
AL Alu-jacket
ALS Alu-jacket with silicone sleeve
B timer function
C plastic housing
D timer-, and turbo function, diagnostic input- and output
E timerfunction, diagnostic input- and output
F stability output
K short circuit proof
L function controller with LED display
LS operation- and stability indicators by LED's
MS metal sleeve made of nickel-plated brass
P PVC-jacket
PU PUR-Cable
R redlight source
S active surface, side
St metal sleeve made of stainless steel
T timer-, and turbo function, diagnostic output
U selectable operation mode
V active surface, front
Z timerfunction and  diagnostic output

 

General Electrical Data:  DC-Version
  INSOR®,
CASOR®,
MINSOR®
OPTOR®
individ. current input < 15 mA < 50 mA
residual stress < 2,5 V < 2,5 V
hysteresis > 1 % ... < 15 % < 20 %
temperature drift < 10 % < 15 %

 

General Electrical Data:  AC-Version
 

INSOR®,
CASOR®,
MINSOR®

OPTOR®

min. load current > 10 mA -
noload current < 2,5 mA < 10 mA
voltage drop < 4,5 V < 3 V

 

Timer Function:
When altering the optical path length switching condition changes in a delayed manner (adjustment).
Turbo Function:
Increases light intensity of emitter for an easier adjustment.
Diagnostic Input:
The diagnostic input allows a controlled switch-off of the emitter, which can be used for function control of the sensor
Diagnostic Output:
The diagnostic output is active when light intensity is in the range of ± 20 % of the switching level.